MCB
Welcome to Clarian UK Ltd website.

MCB – BM SERIES BMS0 4,5 kA
- Rated voltage/frequency
- 230 V/400 V AC 50/60 Hz, 240 V/415 V AC 50/60 Hz ME version
- Rated breaking capacity
- 4.5 kA according to IEC/EN 60 898
- Rated breaking capacity DC
- max 48 V one pole
- Tripping characteristics
- B, C according to EN 60 898
- Back up fuse
- 80 A gG max (>45 kA)
- Tripping temperature
- -5 deg C to +40 deg C
- Operation temperature
- -40 deg C to +75 deg C
- Ambient temperature
- +50 deg C for ME-type
- Selectivity class:
- 3
- Degree of protection
- IP20
- Endurance
- > 8000 Operating cycles
- Window with contact position indicator (Red/Green for each pole)
- Terminal capacity
- 1 mm2 - 25 mm2 (except 1P+N)
- Additional connection cabability for busbar block system
- DIN rail mounting (EN 50 022)
- Finger and hand touch safe according to BVG A3/OVE-EN 6
MCB – BM SERIES BMS0 6 kA
- Rated voltage/frequency
- 230 V/400 V AC 50/60 Hz, 240 V/415 V AC 50/60 Hz ME version
- Rated breaking capacity
- 6 kA according to IEC/EN 60 898, 10 kA according to IEC/EN 60 947-2
- Rated breaking capacity DC
- max 48 V one pole
- Tripping characteristics
- B, C according to EN 60 898
- Back up fuse
- 100 A gG max (>10 kA)
- Tripping temperature
- -5 deg C to +40 deg C
- Operation temperature
- -40 deg C to +75 deg C
- Ambient temperature
- +50 deg C for ME-type
- Selectivity class
- 3 • Degree of protection: IP20
- Endurance
- > 8000 Operating cycles
- Window with contact position indicator (Red/Green for each pole)
- Terminal capacity
- 1 mm2 - 25 mm2
- Additional connection cabability for busbar block system
- DIN rail mounting (EN 50 022)
- Finger and hand touch safe according to BVG A3/OVE-EN 6
MCB – BM SERIES BMS0 10 kA
- Rated voltage/frequency
- 230 V/400 V AC 50/60 Hz
- Rated breaking capacity
- 10 kA according to IEC/EN 60 898, 15 kA according to IEC/EN 60 947-2
- Rated breaking capacity DC
- max 48 V one pole
- Tripping characteristics
- B, C, D according to EN 60 898
- Back up fuse
- 100 A gG max (>10 kA)
- Tripping temperature
- -5 deg C to +40 deg C
- Operation temperature
- -40 deg C to +75 deg C
- Ambient temperature
- +50 deg C for ME-type
- Selectivity class
- 3
- Degree of protection
- IP20
- Endurance
- > 8000 Operating cycles
- Window with contact position indicator (Red/Green for each pole)
- Terminal capacity
- 1 mm2 - 25 mm2 (except 1P+N)
- Additional connection cabability for busbar block system
- DIN rail mounting (EN 50 022)
- Finger and hand touch safe according to BVG A3/OVE-EN 6
MCB – SERIES BMS0-DC
- Rated voltage
- 220 V DC per pole; T = 4 ms
- Switching capacity
- 6 kA acc. to IEC/EN 60898
- Back-up fuse max.
- 100 A gL
- Tripping characteristics
- C
- Terminal capacity
- 1-25 mm2
- Take in account polarity
- Designed for use in DC installations
MCB – BS 1+N SERIES SI-E 4,5 kA / 6 kA
- 1+N at only 1 space unit, Selectivity class
- 3
- Rated voltage/frequency
- 230 V AC, 50/60 Hz
- Rated breaking capacity
- 4,5 kA according to IEC/EN 60 898, 6 kA according to IEC/EN 60 898
- Rated breaking capacity DC
- max 48 V
- Tripping characteristics
- B, C according to EN 60 898
- Back up fuse
- 4,5 kA - Type 80 A gG max (>4,5 kA), 6 kA - Type100 A gG max (>10 kA)
- Tripping temperature
- -5 deg C to +40 deg C
- Operation temperature
- -40 deg C to +75 deg C
MCB – HIGH CURRENT SERIES BR 10 kA
- Rated voltage/frequency
- 230 V/400 V AC 50/60 Hz
- Rated breaking capacity
- 10 kA according to marking
- Rated breaking capacity DC
- max 60 V one pole
- Tripping characteristics
- C & D according to EN 60 898
- Back up fuse
- 200 A gG max (>20 kA)
- Tripping temperature
- -5 deg C to +40 deg C
- Endurance
- > 20,000 Operating cycles
- Window with contact position indicator (Red/Green for each pole)
- Terminal capacity
- 2,5 mm2 - 50 mm2
- Double break switching contact
- DIN rail mounting (EN 50 022)
MCB – HIGH CURRENT BR SERIES 15 – 25 kA
- Rated voltage/frequency
- 230 V/400 V AC 50/60 Hz
- Rated breaking capacity
- 15-25 kA according to marking
- Rated breaking capacity DC
- max 60 V one pole
- Tripping characteristics
- C & D according to EN 60 898
- Back up fuse
- 200 A gG max (>20 kA)
- Tripping temperature
- -5 deg C to +40 deg C
- Degree of protection
- IP20
- Endurance
- > 20,000 Operating cycles
- Window with contact position indicator (Red/Green for each pole)
- Terminal capacity
- 2,5 mm2 - 50 mm2
- Double break switching contact